④ Optional 4-20mA + Hart output ⑤ switching signal
receiving device
User computer, control alarm, PLC, DCS, mobile phone, tablet computer, etc. are optional
Alarm mode
On-site sound and light alarm, external alarm, remote Controller alarm, computer data collection software alarm, mobile app notification, SMS alarm optional
Shell material
Die casting aluminum + sand blasting oxidation/fluorocarbon paint, explosion-proof and anti-corrosion
Operating temperature
-30~50℃
Environmental humidity
0~95% RH non-condensing
Operating Pressure
0~100Kpa
Power Supply
24VDC(12~30VDC)
Dimension
200*149*79mm
Weight
1.5Kg
execution standard
GB3836.1-2010、GB3836.2-2010
MOT500-EX-Y (high temperature)
Gas Detector (high temperature)
EX, range 0~100% LEL, resolution 0.1% LEL, Response time T90 ≤ 20s, detection accuracy ≤ +/- 3%, Linearity ≤ +/- 1%, explosion-proof mark CNEx16.0547, Protection level IP65
Introduction
MOT500 online combustible Gas Detector is suitable for combustible gas concentration detection in various environments. It adopts imported catalytic combustion sensor and microcontroller technology, with fast response speed, high measurement accuracy, good stability and repeatability, and the performance of the whole machine ranks first Chinese professional level.
[Note]Because the manufacturer's packaging may be updated or upgraded, the detailed packaging list shall be subject to the latest standard configuration of the manufacturer.
FAQ
QI want to do a test about the GB16808 standard. Is this combustible Gas detector OK?