Wall-mounted, pipeline type (thread size: M40X1.5mm), circulation type
signal output
① 4-20mA signal: standard 16-bit Accuracy 4-20mA output chip, transmission distance 1Km ② RS485 signal: using standard MODBUS RTU protocol, transmission distance 2Km ③ Voltage signal: 0-5V, 0-10V output, can be set by yourself
signal output
④ Optional 4-20mA + Hart output ⑤ Switching signal: standard 2 sets of relays, optional third set of relays, passive touchpoint, Capacity 220VAC 3A/24VDC 3A
transmission method
① Cable transmission: 3-core, 4-core cable, long-distance transmission (1-2 kilometers) ② TCP/IP transmission: support TCP/IP protocol, use optical fiber and network cable, long-distance real-time transmission through intranet and extranet (optional)
transmission method
③ GPRS transmission: built-in GPRS module, real-time remote data transmission, no distance limit (optional) ④ Wireless transmission: support 433Mhz, radio transmission mode, transmission distance 2-10Km, depending on different Power (optional)
receiving device
User computer, control alarm, PLC, DCS, mobile phone, tablet computer, etc. are optional
Alarm mode
On-site sound and light alarm, external alarm, remote Controller alarm, computer data collection software alarm, mobile app notification, SMS alarm optional
Alarm settings
① Standard configuration two-level alarm, optional three-level alarm ② Gas Sensors can set two alarm modes of conventional high and low alarm and interval control, which can control the concentration range of gas ③ Temperature sensor can set the control range ④ Humidity Sensors can set the control range
shell material
Die casting aluminum + sand blasting oxidation/fluorocarbon paint, explosion-proof and anti-corrosion
Operating temperature
-30~50 ℃ (Humidity environment requires customization or optional pretreatment system)
Operating humidity
≤ 95% RH, non-condensing
Working pressure
0 ~ 100Kpa
Power Supply
24VDC(12~30VDC)
size
200*149*79mm(L×W×H)
Weight
1.5Kg
execution standard
GB3836.1-2010 "Explosive environments - Part 1: Equipment - General requirements" GB3836.2-2010 "Explosive environments - Part 2: Equipment protected by flameproof enclosures" d "
optional range
0-100、500、1000、2000、5000、10000、40000ppm
MOT500-CO-Y
Carbon monoxide Detector
Carbon monoxide (CO), imported electrochemistry /NDIR infrared carbon monoxide gas Sensors, Measurement range 0~100ppm, resolution 0.01ppm, Response time ≤ 20 seconds (T90)
Introduction
MOT500 online carbon monoxide Detector is suitable for carbon monoxide concentration detection in various environments. It adopts imported electrochemical/NDIR infrared absorption gas sensor and microcontroller technology, with fast response speed, high measurement accuracy, good stability and repeatability. The performance of the whole machine is at the domestic (CN) professional level.
[Note]Because the manufacturer's packaging may be updated or upgraded, the detailed packaging list shall be subject to the latest standard configuration of the manufacturer.
FAQ
QDoes the carbon monoxide detector meet the specifications of GB3836.4?
A
Model MOT500-CO-Y Carbon Monoxide Detector Compliant