China

BOSEAN GT-B60 Fixed Combustible Gas Detector 0~100%

SE
GT-B60 fixed Gas Detector without display, without alarm. Adopt industrial-grade Sensors, the instrument shell adopts flameproof and explosion-proof structure design, 4-20mA standard signal or directly enter the DOS system
Model:
Certificate

Bosean GT-B60 Fixed Point Gas DetectorSPEC

Bosean GT-B60 Fixed Point Gas DetectorDetails

Bosean GT-B60 Fixed Point Gas DetectorPacking list

SKU
NB016158
range
0 ~ 100% LEL
resolution
1% LEL
Protection class
IP66
Response time
<30s(T90)
Sensors principle
diffusion
Display error
≤ ± 3% LEL
Operating Environment
-10~55 ℃, < 953% no condensation, 86~ 106kPa
Power Supply
DC24V±3.6v
Sensors Life
2 years (depending on the environment)
Explosion-proof sign
Ex d ⅡC T6 Gb
Operating Mode
Long-term continuous work
Size Weight
203*178*92mm(≈1370g)
power consumption
≤2.5w
Connection Cable
3 * 1.5mm2 Shielding Line
GT-B60
Fixed Point Gas Detector
GT-B60 fixed Gas Detector without display, without alarm. Adopt industrial-grade Sensors, the instrument shell adopts flameproof and explosion-proof structure design, 4-20mA standard signal or directly enter the DOS system
BOSEAN GT-B60 Fixed Combustible Gas Detector 0~100% Picture

GT-B60 adopts industrial-grade sensors, and the instrument shell adopts explosion-proof and explosion-proof structure design, which can be widely used in metallurgy, petroleum, chemical industry, municipal and other industries

Baoshian GT-B60 Fixed Point Gas Detector Details Figure 1

Baoshian GT-B60 Fixed Point Gas Detector Details Figure 2

Baoshian GT-B60 Fixed Point Gas Detector Details Figure 3

Baoshian GT-B60 Fixed Point Gas Detector Details Figure 4

Measured gasMeasuring rangeOptional rangeresolutionalarm point
Combustible gas EX0-100%LEL0-100%VOL (infrared)1%LEL, 1%VOLLow: 20 High: 50 %LEL