China

HUIRUIPU HRP-K6000-32 touch screen 32-way gas alarm controller

SE
4-20mA three-wire system, 7-inch color touch screen, standard 32 Detectors, with sound and light alarm prompts, can store 20,000 alarm records, suitable for factories, oil depots, liquefied gas stations, gas stations, gas stations, etc.
$386.00/set
PromotionLoading...
Coupon
Certificate

HuiRuiPu HRP-K6000-32 Line type gas alarm controllerSPEC

HuiRuiPu HRP-K6000-32 Line type gas alarm controllerDetails

HuiRuiPu HRP-K6000-32 Line type gas alarm controllerPacking list

SKU
NB044046
Display
7-Inch color screen
Operation mode
touch operation
Operating Voltage
AC220V±10% 50HZ
backup Power
24V 1.3AH lead-acid battery (optional)
switch output
Four sets of passive relay output, touchpoint Capacity 10A/AC220V
Operating Temp. & RH
-10°C~50°C ≤ 95%RH
System Power
Maximum power consumption 10W (without external devices)
Number of Detectors
32.
Detector connection
4-20mA signal
data upload
RTU-standard modbus protocol
alarm point
Two-level alarm, can be freely set by the user
Alarm indication
Indicator light + LCD display, buzzer alarm tone prompt
Operating Mode
On-site fixed installation, wall hanging
Storage Capacity
It can store 20,000 alarm record messages
Appearance size
Size 245 * 340 * 90 (mm)
wiring specification
3 wires need to be connected. It is recommended to use ≥ RVVP2 * 1.5 national standard Shielding wire, the diameter of the single core wire is ≥ 1.5mm, and the wire length is ≤ 1000m.
HRP-K6000-32
Line type gas alarm controller
4-20mA three-wire system, 7-inch color touch screen, standard 32 Detectors, with sound and light alarm prompts, can store 20,000 alarm records, suitable for factories, oil depots, liquefied gas stations, gas stations, gas stations, etc.
HUIRUIPU HRP-K6000-32 touch screen 32-way gas alarm controller  Picture

Introduction

The split-line gas detection and alarm controller is used to detect the content of flammable gases or toxic gases in the air, supports multiple 4-20mA signal input, and at the same time centrally controls multiple points. The system adopts a microprocessor as the Control Unit. When the concentration of flammable gases in the environment reaches or exceeds the preset value, the controller immediately emits sound and light alarms, and can drive exhaust or other peripheral actions through relays to prevent explosions and fire accidents, thereby protecting life. The system can be widely used in factories, oil depots, liquefied gas stations, gas stations, gas stations, paint spray rooms and other places that need fire protection and explosion-proof, for safety monitoring and alarming.

Operation panel

HUIRUIPU HRP-K6000-X8 Eight-way gas alarm controller, button model Figure 1


[OK] key: enter the menu or OK function

[Up] key: select menu item or shift operation

[Down] key: select menu item or change value

[Exit] key: return to the previous level menu or exit, it is also the [muffler] function when static. Indicator light: low report, high report, fault, power supply.